DC wiring for solar panels is not sized the same way as standard electrical wiring. Solar panels behave as current sources — under certain fault or irradiance conditions, they can produce current continuously at or above their rated short-circuit current (Isc). This is why solar DC wire sizing uses a higher safety multiplier than typical load wiring.
| Standard | Multiplier | Reasoning |
|---|---|---|
| NEC 690.8(A) — wire ampacity | Isc × 1.25 × 1.25 = ×1.56 | 125% for continuous duty + 125% for temperature/conduit derating |
| AS 4509.2 — overcurrent device | Isc × 1.25 | Minimum fuse/breaker rating for string protection |
| PEC 2017 (aligned with NEC) | Isc × 1.56 | Same as NEC for PV source circuits |
A 550W mono panel typically has Isc = 13.8A. For a single string:
| Step | Calculation | Value |
|---|---|---|
| Panel Isc | From datasheet | 13.8A |
| Minimum wire rating (NEC 690.8) | 13.8A × 1.56 | 21.5A minimum |
| Standard PV cable selected | 6mm² PV1-F (rated 44A) | ✅ 44A > 21.5A |
| For 2 parallel strings | (13.8A × 2) × 1.56 | 43.1A minimum → 6mm² just meets, use 10mm² |
| Cable Type | Temperature Rating | UV Resistance | Use Case |
|---|---|---|---|
| PV1-F (TÜV certified) | 90°C | ✅ Yes — outdoor rated | Rooftop string wiring |
| THHN (standard PH wire) | 75°C | ❌ No — requires conduit | Indoor conduit runs only |
| USE-2 (US standard) | 90°C | ✅ Yes | Underground DC runs |
Always use PV1-F or equivalent solar-rated cable for exposed rooftop DC wiring. Standard THHN will degrade and crack within 3–5 years under Philippine UV and heat conditions.